The standard fiber color code runs blue, orange, green, brown, slate, white, red, black, yellow, violet, rose and aqua for fibers 1 through 12.
ANSI/TIA-598-D-1 extends the code for 16-fiber ribbons and cables. Fibers 13 through 16 are olive, magenta, tan and lime.
Higher-speed optics that use eight lanes in each direction need 16 fibers on one connector. MPO-16 connectivity and 16-fiber ribbons follow from that. As these optics spread through data centers, splicers see 16-fiber ribbon more often.
The standard defines the colors, but manufacturers apply them in different ways. Some mark ribbon fibers with colored inks, some use dashes or rings, and some number the ribbon instead. Always check the manufacturer's data sheet for the cable in front of you, and confirm fiber position before you splice, especially when you mix ribbon from different makers.
Olive, magenta, tan and lime under ANSI/TIA-598-D-1.
No. The colors are standardized, but marking methods vary, so check the manufacturer's data sheet.